BMS2XX CAN protocol

Communication settings​

  • CAN 2.0B, standard 11-bit identifiers; ISO 11898 physical layer.
  • Default speed: 250 kbit/s. Message types and identifiers are CANopen-compatible.
  • Multibyte values use little-endian byte order; signed values use two's complement.
  • The base BMS2XX Node ID is 0x10. The table lists identifiers for this Node ID.

Messages​

IDMessageDirectionLengthInterval
0x190Status 1 (TPDO1)BMS → all8 bytes100 ms
0x290Status 2 (TPDO2)BMS → all8 bytes100 ms
0x490Identification (TPDO4)BMS → all8 bytes1000 ms

Status 1 — 0x190​

BytesTypeContents
0–1u16Status flags
2u8State of charge (SOC): 1 %/bit, 0–100 %; 0xFF means unavailable
3–7—Reserved

A set bit indicates an active flag.

BitMeaning
0General fault
1Pre-fault
2Post-fault
3Overtemperature
4Undertemperature
5Overvoltage
6Undervoltage
7Overcurrent
8Charging
9Charger connected
10Balancing
11Reserved
12Normal charge
13Low charge
14Very low charge
15Battery depleted

Status 2 — 0x290​

BytesTypeContents
0–1u16System voltage, 0.1 V/bit; 0xFFFF means unavailable
2–3i16System current, 0.1 A/bit; 0x8000 (−32768) means unavailable
4i8Minimum temperature, 1 °C/bit; 0x80 (−128) means unavailable
5i8Maximum temperature, 1 °C/bit; 0x80 (−128) means unavailable
6–7—Reserved

Positive current flows into the battery (charging); negative current flows out (discharging). Check sentinel values before applying the scale.

Minimum and maximum temperatures are calculated across all sensors with valid readings. Missing sensors and invalid readings are excluded. With one valid reading, both values equal that reading; with no valid readings, both fields contain 0x80.

Identification — 0x490​

BytesTypeContents
0–3u32Device UID
4u8Hardware revision
5u8Firmware major version
6u8Firmware minor version
7u8Firmware patch version