| General | Configuration version | Structure version; read only. | 0–255 |
| General | Cell voltage sensor count | Number of cell-voltage channels used by the algorithms. | 1–32 |
| General | Temperature sensor count | Number of temperature channels used by the algorithms. | 0–6 |
| General | Temperature sensor type | NTC model for converting resistance to temperature. | TDK B57164K0103J000 (10k, B4300); TDK B57164K0104J000 (100k, B4600); Vishay CM-0603X103F3380FB (100k, B3380) |
| Model | Model name | Battery model name; read only. | String, 16 bytes |
| Model | Nominal capacity | Cell capacity for the model and state estimation. | 0–10 000 Ah |
| Model | Discharge efficiency | Coulombic efficiency during discharge. | 0–100 % |
| Model | Charge efficiency | Coulombic efficiency during charge. | 0–100 % |
| Model | OCV-SOC table entry count | Number of active OCV–SOC table points. | 0–20 |
| Model | OCV point (×20) voltage | Open-circuit voltage for OCV–SOC point. | 0–5000 mV |
| Model | OCV point (×20) SOC | State-of-charge value for OCV–SOC point. | 0–100 % |
| Model | OCV point (×20) temp correction | Temperature correction coefficient for OCV–SOC point. | −10–10 mV/K |
| Model | Reference temperature | Reference temperature for the model and OCV–SOC table. | −40–85 °C |
| Model | Ohmic resistance | Cell ohmic resistance in the model. | 0–1000 mOhm |
| Model | Diffusion capacitance | Diffusion-branch capacitance in the model. | 0–4000 F |
| Model | Diffusion resistance | Diffusion-branch resistance in the model. | 0–1000 mOhm |
| Model | Polarization decay rate | Polarization decay coefficient. | 0–100 % |
| Model | Base hysteresis voltage | Base hysteresis voltage in the model. | −1000–1000 mV |
| Model | Hysteresis gain | Hysteresis gain in the model. | −1000–1000 mV |
| Model | Lower OCV bound | Lower OCV bound for simplified SOC estimation. | 0–5000 mV |
| Model | Upper OCV bound | Upper OCV bound for simplified SOC estimation. | 0–5000 mV |
| State estimation | Minimum SOC for resistance estimation | Minimum SOC for resistance estimation. | 0–100 % |
| State estimation | Maximum SOC for resistance estimation | Maximum SOC for resistance estimation. | 0–100 % |
| State estimation | Resistance estimation window start | Start of the sampling window. | 0–60 s |
| State estimation | Resistance estimation window end | End of the sampling window. | 0–60 s |
| State estimation | Maximum current delta for resistance estimation | Maximum current change for a valid sample. | 0–1000 A |
| State estimation | Resistance estimate EMA factor | Exponential smoothing of the resistance estimate. | 0–255 |
| State estimation | Minimum resistance clamp | Lower bound of the resistance estimate. | 0–1000 mOhm |
| State estimation | Maximum resistance clamp | Upper bound of the resistance estimate. | 0–1000 mOhm |
| Power Flow | Idle current threshold | Absolute current below which the pack is idle. | 0–100 A |
| Protection and thermal comparators | Enable | Enable each comparator independently. | On / off |
| Protection and thermal comparators | Trip threshold | Threshold for entering the state. | As listed below |
| Protection and thermal comparators | Trip delay | Time beyond the trip threshold before activation. | 0–3600 s |
| Protection and thermal comparators | Release threshold | Threshold for leaving the state. | As listed below |
| Protection and thermal comparators | Release delay | Time beyond the release threshold before clearing the state. | 0–3600 s |
| Primary and secondary protection | Overvoltage | Cell-voltage thresholds; independent for both protections. | 0–5000 mV |
| Primary and secondary protection | Undervoltage | Cell-voltage thresholds; independent for both protections. | 0–5000 mV |
| Primary and secondary protection | Overcurrent charge | Independent primary and secondary protection comparators. | −1000–1000 A |
| Primary and secondary protection | Overcurrent discharge | Independent primary and secondary protection comparators. | −1000–1000 A |
| Primary and secondary protection | Overtemperature charge | Independent primary and secondary protection comparators. | −40–125 °C |
| Primary and secondary protection | Overtemperature discharge | Independent primary and secondary protection comparators. | −40–125 °C |
| Primary and secondary protection | Undertemperature charge | Independent primary and secondary protection comparators. | −40–125 °C |
| Primary and secondary protection | Undertemperature discharge | Independent primary and secondary protection comparators. | −40–125 °C |
| Primary and secondary protection | Overpower charge | Independent primary and secondary protection comparators. | −1 000 000–1 000 000 W |
| Primary and secondary protection | Overpower discharge | Independent primary and secondary protection comparators. | −1 000 000–1 000 000 W |
| Primary and secondary protection | Contactor overtemperature | Independent primary and secondary protection comparators. | −40–125 °C |
| Primary and secondary protection | Connector overtemperature | Independent primary and secondary protection comparators. | −40–125 °C |
| Thermal Management | Heater | Independent thermal control comparator. | −40–125 °C |
| Thermal Management | Cooler | Independent thermal control comparator. | −40–125 °C |
| Thermal Management | Condensation prevention | Independent thermal control comparator. | −40–125 °C |
| Balancer | Balancing strategy | Strategy that determines when balancing starts. | Off; Voltage top; Voltage bottom; Voltage any; SOC any |
| Balancer | Balancing cell count | Number of cells managed by the balancer. | 1–32 |
| Balancer | Balance voltage threshold | Cell-voltage threshold for starting balancing. | 0–5000 mV |
| Balancer | Balance voltage difference trip | Cell-voltage difference that starts balancing. | 0–1000 mV |
| Balancer | Balance voltage difference release | Cell-voltage difference that stops balancing. | 0–1000 mV |
| Balancer | Balance SOC difference trip | SOC difference that starts SOC-based balancing. | 0–100 % |
| Balancer | Balance SOC difference release | SOC difference that stops SOC-based balancing. | 0–100 % |
| Contactors | Contactor topology | Power topology used by the contactor state machine. | Main positive, load precharge: charge/discharge MOSFETs with one or two ports; separate bidirectional contactors with two ports; shared bidirectional contactor with one port. |
| Contactors | Precharge timeout | Maximum precharge duration. | 0–60 s |
| Contactors | Precharge completion threshold | Voltage ratio required to complete precharge. | 0–100 % |
| BMS Status Flags | Low SOC threshold | SOC threshold for the BSF_LOW_SOC flag. | 0–100 % |
| BMS Status Flags | High SOC threshold | SOC threshold for the BSF_HIGH_SOC flag. | 0–100 % |
| Discrete I/O | DI1–DI4 | Function of each channel. | Off; Charger connector; Load connector; Battery enclosure (lid/door); Battery power; Charger lid; Interlock; Main positive load aux; Main positive charger aux; Main positive aux; Main negative load aux; Main negative charger aux; Main negative aux; Precharge load aux; Precharge charger aux; Precharge aux; Emergency stop; External enable; PCS ready; Fire alarm |
| Discrete I/O | DO1–DO4 / PDO1–PDO4 | Function of each channel. | Off; BMS on; Discharge enabled; Charge enabled; Protection; Charger control; Low SOC; High SOC; Heater; Cooler |
| Discrete I/O | DI / DO / PDO | Invert each channel’s electrical level. | On / off |
| Charger | Charge control mode | Control law for limiting charger output. | CC; CP; CCCV; CPCV |
| Charger | Charger protocol | Control interface for the external charger. | Off; Discrete on/off; PWM; CAN Faraday; CAN J1939; CAN GB/T 27930 |
| Charger | Max charge current | Maximum current requested from the charger. | 0–1000 A |
| Charger | Max charge voltage | Maximum voltage requested from the charger. | 0–1000 V |
| Charger | Max charge power | Maximum power requested from the charger. | 0–1 000 000 W |
| Charger | Charger timeout | Maximum time without communication or control updates. | 0–600 s |
| Charger | CV taper start cell voltage | Cell voltage at which CV current tapering starts. | 0–5000 mV |
| Charger | CV taper end cell voltage | Cell voltage at which tapering reaches minimum current. | 0–5000 mV |
| Charger | Min charge current | Current at the end of the taper region. | 0–1000 A |